B-38
C70 Capacitor Bank Protection and Control System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
9A19
FlexElement™ 13 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9A1B
FlexElement™ 14 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9A1D
FlexElement™ 15 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
9A1F
FlexElement™ 16 Actual
-2147483.647 to 2147483.647
---
0.001
F004
0
Capacitor control settings (read/write, 4 modules)
9C00
Capacitor control 1 function
0 to 1
---
1
F102
0 (Disabled)
9C01
Capacitor control 1 set remote 1
0 to 65535
---
1
F300
0
9C02
Capacitor control 1 set remote 2
0 to 65535
---
1
F300
0
9C03
Capacitor control 1 set local 1
0 to 65535
---
1
F300
0
9C04
Capacitor control 1 set local 2
0 to 65535
---
1
F300
0
9C05
Capacitor control 1 remote control enable
0 to 65535
---
1
F300
0
9C06
Capacitor control 1 local control enable
0 to 65535
---
1
F300
0
9C07
Capacitor control 1 remote set automatic
0 to 65535
---
1
F300
0
9C08
Capacitor control 1 local set automatic
0 to 65535
---
1
F300
0
9C09
Capacitor control 1 remote set manual
0 to 65535
---
1
F300
0
9C0A
Capacitor control 1 local set manual
0 to 65535
---
1
F300
0
9C0B
Capacitor control 1 trip 1
0 to 65535
---
1
F300
0
9C0C
Capacitor control 1 trip 2
0 to 65535
---
1
F300
0
9C0D
Capacitor control 1 trip 3
0 to 65535
---
1
F300
0
9C0E
Capacitor control 1 trip 4
0 to 65535
---
1
F300
0
9C0F
Capacitor control 1 trip 5
0 to 65535
---
1
F300
0
9C10
Capacitor control 1 trip 6
0 to 65535
---
1
F300
0
9C11
Reserved
---
---
---
---
---
9C12
Capacitor control 1 automatic control enable
0 to 65535
---
1
F300
0
9C13
Capacitor control 1 manual control enable
0 to 65535
---
1
F300
0
9C14
Capacitor control 1 remote open
0 to 65535
---
1
F300
0
9C15
Capacitor control 1 local open
0 to 65535
---
1
F300
0
9C16
Capacitor control 1 automatic open
0 to 65535
---
1
F300
0
9C17
Capacitor control 1 breaker open 52b
0 to 65535
---
1
F300
0
9C18
Capacitor control 1 trip seal-in delay
0 to 60.000
s
0.001
F001
400
9C19
Capacitor control 1 remote close
0 to 65535
---
1
F300
0
9C1A
Capacitor control 1 local close
0 to 65535
---
1
F300
0
9C1B
Capacitor control 1 automatic close
0 to 65535
---
1
F300
0
9C1C
Capacitor control 1 breaker closed 52a
0 to 65535
---
1
F300
0
9C1D
Capacitor control 1 close discharge time
0 to 3600
s
1
F001
300
9C1F
Capacitor control 1 close seal-in delay
0 to 60.000
s
0.001
F001
400
9C20
Capacitor control 1 breaker close block
0 to 65535
---
1
F300
0
9C21
Reserved
---
---
---
---
---
9C22
Capacitor control 1 targets
0 to 2
---
1
F109
0 (Self-Reset)
9C23
Capacitor control 1 events
0 to 1
---
1
F102
0 (Disabled)
9C24
...Repeated for capacitor control element 2
9C48
...Repeated for capacitor control element 3
9C6C
...Repeated for capacitor control element 4
Automatic voltage regulator settings (read/write, 3 modules)
9C90
Automatic voltage regulator 1 function
0 to 1
---
1
F102
0 (Disabled)
9C91
Automatic voltage regulator 1 source
0 to 5
---
1
F167
0 (SRC 1)
9C92
Automatic voltage regulator 1 minimum voltage
0.500 to 15.000
pu
0.001
F001
500
9C93
Automatic voltage regulator 1 control mode
0 to 1
---
1
F536
0 (Voltage)
9C94
Automatic voltage regulator 1 voltage operating signal
0 to 5
---
1
F535
4 (V1)
9C95
Automatic voltage regulator 1 voltage level to close
0.750 to 1.500
pu
0.001
F001
950
9C96
Automatic voltage regulator 1 voltage level to open
0.750 to 1.500
pu
0.001
F001
1050
9C97
AVR 1 voltage drop compensation impedance
0 to 250
ohms
0.01
F001
0
9C98
AVR 1 voltage drop compensation RCA
30 to 90
°
1
F001
75
9C99
Automatic voltage regulator 1 var level to close
–1.500 to 1.500
pu
0.001
F002
950
Table B–9: MODBUS MEMORY MAP (Sheet 31 of 53)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание UR Series C70
Страница 2: ......
Страница 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C70 Capacitor Bank Protection and Control System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 124: ...4 30 C70 Capacitor Bank Protection and Control System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...8 18 C70 Capacitor Bank Protection and Control System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 414: ...9 18 C70 Capacitor Bank Protection and Control System GE Multilin 9 1 OVERVIEW 9 THEORY OF OPERATION 9 ...
Страница 436: ...10 22 C70 Capacitor Bank Protection and Control System GE Multilin 10 4 SETTING EXAMPLE 10 APPLICATION OF SETTINGS 10 ...
Страница 547: ...GE Multilin C70 Capacitor Bank Protection and Control System B 79 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 548: ...B 80 C70 Capacitor Bank Protection and Control System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Страница 598: ...E 12 C70 Capacitor Bank Protection and Control System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...