GE Multilin
C70 Capacitor Bank Protection and Control System
9-13
9 THEORY OF OPERATION
9.1 OVERVIEW
9
Figure 9–6: NEUTRAL CURRENT UNBALANCE APPLICATION
The neutral current unbalance protection uses the following operate signal.
(EQ 9.54)
The neutral current unbalance protection uses the following restraint signal.
(EQ 9.55)
In the above equations,
k
1
represents the vector capacitor bank positive sequence inherent unbalance factor setting, and
k
1
* represents the complex conjugate of
k
1
. The currents are as defined in the figure above, and are in per-unit values of
the nominal current of the bank source ground current channel.
These equations involve phasors, not magnitudes; that is, the vector sum of the currents is created by the protection func-
tion implementing the method. The protection operates when the operate signal is greater than the set pickup level for the
set pickup delay.
Sensitivity is the key performance parameter. The applied comparator uses a simple integration method in addition to the
standard hysteresis approach, to deal with chattering of the operating signal at the boundary of operation.
b) BALANCED CASE
The currents in the neutral current unbalance protection are driven by the individual admittances in each string:
834748A1.CDR
I
C1
I
A
I
DIF
window CT
I
N1
C
C1
I
B1
C
B1
I
A1
C
A1
I
C2
I
N2
C
C2
I
B2
C
B2
I
A2
C
A2
I
B
I
C
V
C
V
A
V
B
grounded
configuration
I
DIF
low ratio CT
I
N1
I
N2
V
X
ungrounded
configuration
I
OP
I
DIF
k
1
I
1
k
1
*
I
2
–
–
=
I
REST
I
0
=
Содержание UR Series C70
Страница 2: ......
Страница 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C70 Capacitor Bank Protection and Control System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 124: ...4 30 C70 Capacitor Bank Protection and Control System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...8 18 C70 Capacitor Bank Protection and Control System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 414: ...9 18 C70 Capacitor Bank Protection and Control System GE Multilin 9 1 OVERVIEW 9 THEORY OF OPERATION 9 ...
Страница 436: ...10 22 C70 Capacitor Bank Protection and Control System GE Multilin 10 4 SETTING EXAMPLE 10 APPLICATION OF SETTINGS 10 ...
Страница 547: ...GE Multilin C70 Capacitor Bank Protection and Control System B 79 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 548: ...B 80 C70 Capacitor Bank Protection and Control System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Страница 598: ...E 12 C70 Capacitor Bank Protection and Control System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...