GE Multilin
C70 Capacitor Bank Protection and Control System
7-3
7 COMMANDS AND TARGETS
7.1 COMMANDS
7
c) NEUTRAL VOLTAGE UNBALANCE
PATH: COMMANDS
Ö
CAPACITOR BANK AUTO...
Ö
NEUTRAL VOLTAGE UNBALANCE
Ö
NEUTRAL VOLTAGE UNBALANCE 1(3)
The auto-setting feature shall be used when the capacitor bank is on-line and the 59NU function is enabled. For security
reasons, it may be necessary to consider applying less sensitive settings during the auto-setting process. Switching tempo-
rarily to a different setting group with less sensitive pickup thresholds is a method to provide for this extra security.
This feature can be used with a manual acceptance of the auto-calculated coefficients (the
NTRL VOL UNBAL 1 AUTO SET
command switched to “Manual”), or with an automatic acceptance of the calculated factors (the
NTRL VOL UNBAL 1 AUTO
SET
command switched to “Auto”).
The feature is used as follows.
MANUAL SUPERVISION OF AUTOMATICALLY CALCULATED FACTORS:
When the
NTRL VOL UNBAL 1 AUTO SET
command is switched to “Manual”, the auto-setting screens (one for each of the two
factors) display values that best balance the function and prompt for permission to apply the calculated value as a new set-
ting. When confirmed, the auto-selected value is applied to all setting groups having same source as the active group dur-
ing auto-setting procedure. Both ratios (
X
A
/
X
B
and
X
A
/
X
C
) must be set correctly to clear the inherent bank unbalance.
After consent to apply the calculated coefficient is received via the keypad, the
k =?.???? APPLIED
confirmation message is
displayed for the duration of the flash message time. The time-out period is intended for field staff to make a note of the
newly applied coefficient. However, it is possible to immediately navigate from this screen. The new setting values can be
viewed in the
SETTING
menu at any time.
After the process if finished, it is recommended to disable the auto-setting feature. If not manually disabled, the feature
automatically disables itself when user-initiated front panel interface activity ceases and the C70 display is dimmed.
Certain security conditions are checked during the auto-setting process, such as the deviation from the nominal frequency
and the magnitude of the phase voltages within 0.85 pu and 1.15 pu. If any of these conditions are violated, the
SUPV FAIL
message is displayed in the second line.
If the neutral voltage unbalance function is disabled or blocked, the auto-setting process is not functional and the
59NU NOT
RUNNING
message is displayed in the second line.
AUTOMATIC SUPERVISION OF AUTOMATICALLY CALCULATED FACTORS:
When the
NTRL VOL UNBAL 1 AUTO SET
command is switched to “Auto”, the process of calculating and applying the balanc-
ing coefficients is fully automatic. Typical applications require setting this function to “Auto” with the bank de-energized,
then energizing the capacitor bank. After the function is set to “Auto”, it expects to read valid input signals as a result of
bank energization within the display flash message time duration to calculate and apply factors; otherwise, the function is
returned to “Disabled”. When the bank is energized and the five-cycle timer of the 59NU function expires, the balancing
coefficients are calculated and automatically applied. When the new balancing factors are applied, the function switches
automatically from “Auto” to “Disabled” and the 59NU function becomes operational. In essence, the when in the “Auto”
mode, the confirmation command is automatically executed immediately after the balancing values are available. The C70
does not display the applied coefficients in the “Auto” mode; rather, they are be viewed in the
SETTINGS
menu.
When the supervisory conditions are not satisfied in “Auto” mode, the
AUTO FAIL
message is displayed and the 59NU func-
tion starts running with the pre-existing settings for the balancing factors.
NEUTRAL VOLTAGE
UNBALANCE 1
NTRL VOL UNBAL 1
AUTO SET: Disabled
Range: Disabled, Manual, Auto
MESSAGE
XA/XB RATIO k=0.0000
APPLY? No
Range: Yes, No
MESSAGE
XA/XC RATIO k=0.0000
APPLY? No
Range: Yes, No
Содержание UR Series C70
Страница 2: ......
Страница 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C70 Capacitor Bank Protection and Control System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 124: ...4 30 C70 Capacitor Bank Protection and Control System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...8 18 C70 Capacitor Bank Protection and Control System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 414: ...9 18 C70 Capacitor Bank Protection and Control System GE Multilin 9 1 OVERVIEW 9 THEORY OF OPERATION 9 ...
Страница 436: ...10 22 C70 Capacitor Bank Protection and Control System GE Multilin 10 4 SETTING EXAMPLE 10 APPLICATION OF SETTINGS 10 ...
Страница 547: ...GE Multilin C70 Capacitor Bank Protection and Control System B 79 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 548: ...B 80 C70 Capacitor Bank Protection and Control System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Страница 598: ...E 12 C70 Capacitor Bank Protection and Control System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...