B-20
C70 Capacitor Bank Protection and Control System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
4147
DNP object 32 default variation
0 to 5
---
1
F525
0 (1)
Ethernet switch (Read/Write Setting)
4148
Ethernet switch IP address
0 to 4294967295
---
1
F003
3232235778
414A
Ethernet switch Modbus IP port number
1 to 65535
---
1
F001
502
414B
Ethernet switch Port 1 Events
0 to 1
---
1
F102
0 (Disabled)
414C
Ethernet switch Port 2 Events
0 to 1
---
1
F102
0 (Disabled)
414D
Ethernet switch Port 3 Events
0 to 1
---
1
F102
0 (Disabled)
414E
Ethernet switch Port 4 Events
0 to 1
---
1
F102
0 (Disabled)
414F
Ethernet switch Port 5 Events
0 to 1
---
1
F102
0 (Disabled)
4150
Ethernet switch Port 6 Events
0 to 1
---
1
F102
0 (Disabled)
Ethernet switch (Read Only Actual Values)
4151
Ethernet switch MAC address
---
---
1
F072
0
4154
Ethernet switch Port 1 Status
0 to 2
---
1
F134
0 (Fail)
4155
Ethernet switch Port 2 Status
0 to 2
---
1
F134
0 (Fail)
4156
Ethernet switch Port 3 Status
0 to 2
---
1
F134
0 (Fail)
4157
Ethernet switch Port 4 Status
0 to 2
---
1
F134
0 (Fail)
4158
Ethernet switch Port 5 Status
0 to 2
---
1
F134
0 (Fail)
4159
Ethernet switch Port 6 Status
0 to 2
---
1
F134
0 (Fail)
415A
Switch Firmware Version
0.00 to 99.99
---
0.01
F001
0
Simple Network Time Protocol (Read/Write Setting)
4168
Simple Network Time Protocol (SNTP) function
0 to 1
---
1
F102
0 (Disabled)
4169
Simple Network Time Protocol (SNTP) server IP address
0 to 4294967295
---
1
F003
0
416B
Simple Network Time Protocol (SNTP) UDP port number
1 to 65535
---
1
F001
123
Data Logger Commands (Read/Write Command)
4170
Data Logger Clear
0 to 1
---
1
F126
0 (No)
Data Logger (Read/Write Setting)
4181
Data Logger Channel Settings (16 items)
---
---
---
F600
0
4191
Data Logger Mode
0 to 1
---
1
F260
0 (continuous)
4192
Data Logger Trigger
0 to 65535
---
1
F300
0
4193
Data Logger Rate
15 to 3600000
ms
1
F003
60000
Clock (Read/Write Command)
41A0
Real Time Clock Set Time
0 to 235959
---
1
F050
0
Clock (Read/Write Setting)
41A2
SR Date Format
0 to 4294967295
---
1
F051
0
41A4
SR Time Format
0 to 4294967295
---
1
F052
0
41A6
IRIG-B Signal Type
0 to 2
---
1
F114
0 (None)
41A7
Clock Events Enable / Disable
0 to 1
---
1
F102
0 (Disabled)
41A8
Time Zone Offset from UTC
–24 to 24
hours
0.5
F002
0
41A9
Daylight Savings Time (DST) Function
0 to 1
---
1
F102
0 (Disabled)
41AA
Daylight Savings Time (DST) Start Month
0 to 11
---
1
F237
0 (January)
41AB
Daylight Savings Time (DST) Start Day
0 to 6
---
1
F238
0 (Sunday)
41AC
Daylight Savings Time (DST) Start Day Instance
0 to 4
---
1
F239
0 (First)
41AD
Daylight Savings Time (DST) Start Hour
0 to 23
---
1
F001
2
41AE
Daylight Savings Time (DST) Stop Month
0 to 11
---
1
F237
0 (January)
41AF
Daylight Savings Time (DST) Stop Day
0 to 6
---
1
F238
0 (Sunday)
41B0
Daylight Savings Time (DST) Stop Day Instance
0 to 4
---
1
F239
0 (First)
41B1
Daylight Savings Time (DST) Stop Hour
0 to 23
---
1
F001
2
Oscillography (Read/Write Setting)
41C0
Oscillography Number of Records
1 to 64
---
1
F001
15
41C1
Oscillography Trigger Mode
0 to 1
---
1
F118
0 (Auto. Overwrite)
41C2
Oscillography Trigger Position
0 to 100
%
1
F001
50
41C3
Oscillography Trigger Source
0 to 65535
---
1
F300
0
41C4
Oscillography AC Input Waveforms
0 to 4
---
1
F183
2 (16 samples/cycle)
41D0
Oscillography Analog Channel
n
(16 items)
0 to 65535
---
1
F600
0
Table B–9: MODBUS MEMORY MAP (Sheet 13 of 53)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание UR Series C70
Страница 2: ......
Страница 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C70 Capacitor Bank Protection and Control System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 124: ...4 30 C70 Capacitor Bank Protection and Control System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...8 18 C70 Capacitor Bank Protection and Control System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 414: ...9 18 C70 Capacitor Bank Protection and Control System GE Multilin 9 1 OVERVIEW 9 THEORY OF OPERATION 9 ...
Страница 436: ...10 22 C70 Capacitor Bank Protection and Control System GE Multilin 10 4 SETTING EXAMPLE 10 APPLICATION OF SETTINGS 10 ...
Страница 547: ...GE Multilin C70 Capacitor Bank Protection and Control System B 79 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 548: ...B 80 C70 Capacitor Bank Protection and Control System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Страница 598: ...E 12 C70 Capacitor Bank Protection and Control System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...