GE Multilin
C70 Capacitor Bank Protection and Control System
6-5
6 ACTUAL VALUES
6.2 STATUS
6
6.2.7 REMOTE DEVICES
a) STATUS
PATH: ACTUAL VALUES
Ö
STATUS
ÖØ
REMOTE DEVICES STATUS
The present state of up to 16 programmed remote devices is shown here. The
ALL REMOTE DEVICES ONLINE
message indi-
cates whether or not all programmed remote devices are online. If the corresponding state is "No", then at least one
required remote device is not online.
b) STATISTICS
PATH: ACTUAL VALUES
Ö
STATUS
ÖØ
REMOTE DEVICES STATISTICS
Ö
REMOTE DEVICE 1(16)
Statistical data (two types) for up to 16 programmed remote devices is shown here.
The
StNum
number is obtained from the indicated remote device and is incremented whenever a change of state of at
least one DNA or UserSt bit occurs. The
SqNum
number is obtained from the indicated remote device and is incremented
whenever a GSSE message is sent. This number will rollover to zero when a count of 4 294 967 295 is incremented.
6.2.8 DIGITAL COUNTERS
PATH: ACTUAL VALUES
Ö
STATUS
ÖØ
DIGITAL COUNTERS
Ö
DIGITAL COUNTERS Counter 1(8)
The present status of the eight digital counters is shown here. The status of each counter, with the user-defined counter
name, includes the accumulated and frozen counts (the count units label will also appear). Also included, is the date and
time stamp for the frozen count. The
COUNTER 1 MICROS
value refers to the microsecond portion of the time stamp.
REMOTE DEVICES
STATUS
All REMOTE DEVICES
ONLINE: No
Range: Yes, No
MESSAGE
REMOTE DEVICE 1
STATUS: Offline
Range: Online, Offline
MESSAGE
REMOTE DEVICE 2
STATUS: Offline
Range: Online, Offline
↓
MESSAGE
REMOTE DEVICE 16
STATUS: Offline
Range: Online, Offline
REMOTE DEVICE 1
REMOTE DEVICE 1
StNum: 0
MESSAGE
REMOTE DEVICE 1
SqNum: 0
DIGITAL COUNTERS
Counter 1
Counter 1
ACCUM:
0
MESSAGE
Counter 1
FROZEN:
0
MESSAGE
Counter 1
FROZEN:
YYYY/MM/DD HH:MM:SS
MESSAGE
Counter 1
MICROS:
0
Содержание UR Series C70
Страница 2: ......
Страница 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C70 Capacitor Bank Protection and Control System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 124: ...4 30 C70 Capacitor Bank Protection and Control System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...8 18 C70 Capacitor Bank Protection and Control System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 414: ...9 18 C70 Capacitor Bank Protection and Control System GE Multilin 9 1 OVERVIEW 9 THEORY OF OPERATION 9 ...
Страница 436: ...10 22 C70 Capacitor Bank Protection and Control System GE Multilin 10 4 SETTING EXAMPLE 10 APPLICATION OF SETTINGS 10 ...
Страница 547: ...GE Multilin C70 Capacitor Bank Protection and Control System B 79 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 548: ...B 80 C70 Capacitor Bank Protection and Control System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Страница 598: ...E 12 C70 Capacitor Bank Protection and Control System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...