GE Multilin
C70 Capacitor Bank Protection and Control System
B-27
APPENDIX B
B.4 MEMORY MAPPING
B
Neutral Time Overcurrent (Read/Write Grouped Setting) (6 modules)
5B00
Neutral Time Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
5B01
Neutral Time Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
5B02
Neutral Time Overcurrent 1 Input
0 to 1
---
1
F122
0 (Phasor)
5B03
Neutral Time Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
5B04
Neutral Time Overcurrent 1 Curve
0 to 16
---
1
F103
0 (IEEE Mod Inv)
5B05
Neutral Time Overcurrent 1 Multiplier
0 to 600
---
0.01
F001
100
5B06
Neutral Time Overcurrent 1 Reset
0 to 1
---
1
F104
0 (Instantaneous)
5B07
Neutral Time Overcurrent 1 Block
0 to 65535
---
1
F300
0
5B08
Neutral Time Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
5B09
Neutral Time Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
5B0A
Reserved (6 items)
0 to 1
---
1
F001
0
5B10
...Repeated for Neutral Time Overcurrent 2
5B20
...Repeated for Neutral Time Overcurrent 3
5B30
...Repeated for Neutral Time Overcurrent 4
5B40
...Repeated for Neutral Time Overcurrent 5
5B50
...Repeated for Neutral Time Overcurrent 6
Neutral Instantaneous Overcurrent (Read/Write Grouped Setting) (12 modules)
5C00
Neutral Instantaneous Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
5C01
Neutral Instantaneous Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
5C02
Neutral Instantaneous Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
5C03
Neutral Instantaneous Overcurrent 1 Delay
0 to 600
s
0.01
F001
0
5C04
Neutral Instantaneous Overcurrent 1 Reset Delay
0 to 600
s
0.01
F001
0
5C05
Neutral Instantaneous Overcurrent 1 Block
0 to 65535
---
1
F300
0
5C06
Neutral Instantaneous Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
5C07
Neutral Instantaneous Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
5C08
Reserved (8 items)
0 to 1
---
1
F001
0
5C10
...Repeated for Neutral Instantaneous Overcurrent 2
5C20
...Repeated for Neutral Instantaneous Overcurrent 3
5C30
...Repeated for Neutral Instantaneous Overcurrent 4
5C40
...Repeated for Neutral Instantaneous Overcurrent 5
5C50
...Repeated for Neutral Instantaneous Overcurrent 6
5C60
...Repeated for Neutral Instantaneous Overcurrent 7
5C70
...Repeated for Neutral Instantaneous Overcurrent 8
5C80
...Repeated for Neutral Instantaneous Overcurrent 9
5C90
...Repeated for Neutral Instantaneous Overcurrent 10
5CA0
...Repeated for Neutral Instantaneous Overcurrent 11
5CB0
...Repeated for Neutral Instantaneous Overcurrent 12
Ground Time Overcurrent (Read/Write Grouped Setting) (6 modules)
5D00
Ground Time Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
5D01
Ground Time Overcurrent 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
5D02
Ground Time Overcurrent 1 Input
0 to 1
---
1
F122
0 (Phasor)
5D03
Ground Time Overcurrent 1 Pickup
0 to 30
pu
0.001
F001
1000
5D04
Ground Time Overcurrent 1 Curve
0 to 16
---
1
F103
0 (IEEE Mod Inv)
5D05
Ground Time Overcurrent 1 Multiplier
0 to 600
---
0.01
F001
100
5D06
Ground Time Overcurrent 1 Reset
0 to 1
---
1
F104
0 (Instantaneous)
5D07
Ground Time Overcurrent 1 Block
0 to 65535
---
1
F300
0
5D08
Ground Time Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
5D09
Ground Time Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
5D0A
Reserved (6 items)
0 to 1
---
1
F001
0
5D10
...Repeated for Ground Time Overcurrent 2
5D20
...Repeated for Ground Time Overcurrent 3
5D30
...Repeated for Ground Time Overcurrent 4
5D40
...Repeated for Ground Time Overcurrent 5
Table B–9: MODBUS MEMORY MAP (Sheet 20 of 53)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание UR Series C70
Страница 2: ......
Страница 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C70 Capacitor Bank Protection and Control System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 124: ...4 30 C70 Capacitor Bank Protection and Control System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...8 18 C70 Capacitor Bank Protection and Control System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 414: ...9 18 C70 Capacitor Bank Protection and Control System GE Multilin 9 1 OVERVIEW 9 THEORY OF OPERATION 9 ...
Страница 436: ...10 22 C70 Capacitor Bank Protection and Control System GE Multilin 10 4 SETTING EXAMPLE 10 APPLICATION OF SETTINGS 10 ...
Страница 547: ...GE Multilin C70 Capacitor Bank Protection and Control System B 79 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 548: ...B 80 C70 Capacitor Bank Protection and Control System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Страница 598: ...E 12 C70 Capacitor Bank Protection and Control System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...