background image

FireBag

®

Use & Care Manual

1-800-899-0553

assured

automation

.com

1. INTRODUCTION

The FireBag automatically turns off gas
supply in the event of fire, preventing
explosions and the spreading of fire. 

When outside temperature reaches 
203˚F to 212˚F (95˚C to 100˚C) the metal
alloy that keeps plug and cartridge
together melts and the spring pressure
pushes the plug against the gas opening
to close it completely. 

No fire or heat detectors are required to
automatically intercept gas flow.

2. GENERAL SPECIFICATIONS

Thermal safety device, FireBag, as a
connection or with integrated interceptor
valve (GT2, G4T or R4T). 

ASSEMBLING IS TO BE EXECUTED BY
AUTHORIZED COMPANIES ONLY. 

Before installation read and follow the
installation instructions.

3. USAGE

The thermal safety device, FireBag, 
shuts off automatically the flow of gas 
in the instance of fire and is certified for
natural gas, city gas, and fluid gas I (in 
gas form). It is manufactured according 
to DIN 3586 Standard.

FB2010

© Assured Automation 2010

Technical Specifications

• Maximum Pressure: 72.5 PSI (NPT), 

232 PSI (Flanged)

• Temperature Range: -4˚F to 176˚F

• Set-off Temperature: 203˚F to 212˚F

• Shut-off time: < 60 sec. 

• Heat Resistance: 1,697˚F for 60 minutes

at 72.5 PSI (NPT)

4. INSTALLATION

1.

Before installation, check that the device
has not gone off (check the integrity of 
the shut-off device and the gas flow).

2.

Protect the valve against dirt before 
usage and during the installation.

Отзывы: