GE Multilin
C70 Capacitor Bank Protection and Control System
C-3
APPENDIX C
C.2 SERVER DATA ORGANIZATION
C
C.2.6 MMXU: ANALOG MEASURED VALUES
A limited number of measured analog values are available through the MMXU logical nodes.
Each MMXU logical node provides data from a C70 current and voltage source. There is one MMXU available for each con-
figurable source (programmed in the
SETTINGS
ÖØ
SYSTEM SETUP
ÖØ
SIGNAL SOURCES
menu). MMXU1 provides data
from C70 source 1, and MMXU2 provides data from C70 source 2.
MMXU data is provided in two forms: instantaneous and deadband. The instantaneous values are updated every time a
read operation is performed by a client. The deadband values are calculated as described in IEC 61850 parts 7-1 and 7-3.
The selection of appropriate deadband settings for the C70 is described in chapter 5 of this manual.
IEC 61850 buffered and unbuffered reporting capability is available in all MMXU logical nodes. MMXUx logical nodes pro-
vide the following data for each source:
•
MMXU1.MX.TotW: three-phase real power
•
MMXU1.MX.TotVAr: three-phase reactive power
•
MMXU1.MX.TotVA: three-phase apparent power
•
MMXU1.MX.TotPF: three-phase power factor
•
MMXU1.MX.Hz: frequency
•
MMXU1.MX.PPV.phsAB: phase AB voltage magnitude and angle
•
MMXU1.MX.PPV.phsBC: phase BC voltage magnitude and angle
•
MMXU1.MX.PPV.phsCA: Phase CA voltage magnitude and angle
•
MMXU1.MX.PhV.phsA: phase AG voltage magnitude and angle
•
MMXU1.MX.PhV.phsB: phase BG voltage magnitude and angle
•
MMXU1.MX.PhV.phsC: phase CG voltage magnitude and angle
•
MMXU1.MX.A.phsA: phase A current magnitude and angle
•
MMXU1.MX.A.phsB: phase B current magnitude and angle
•
MMXU1.MX.A.phsC: phase C current magnitude and angle
•
MMXU1.MX.A.neut: ground current magnitude and angle
•
MMXU1.MX.W.phsA: phase A real power
•
MMXU1.MX.W.phsB: phase B real power
•
MMXU1.MX.W.phsC: phase C real power
•
MMXU1.MX.VAr.phsA: phase A reactive power
•
MMXU1.MX.VAr.phsB: phase B reactive power
•
MMXU1.MX.VAr.phsC: phase C reactive power
•
MMXU1.MX.VA.phsA: phase A apparent power
•
MMXU1.MX.VA.phsB: phase B apparent power
•
MMXU1.MX.VA.phsC: phase C apparent power
•
MMXU1.MX.PF.phsA: phase A power factor
•
MMXU1.MX.PF.phsB: phase B power factor
•
MMXU1.MX.PF.phsC: phase C power factor
C.2.7 PROTECTION AND OTHER LOGICAL NODES
The following list describes the protection elements for all UR-series relays. The C70 relay will contain a subset of protec-
tion elements from this list.
•
PDIF: bus differential, transformer instantaneous differential, transformer percent differential
Содержание UR Series C70
Страница 2: ......
Страница 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C70 Capacitor Bank Protection and Control System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 124: ...4 30 C70 Capacitor Bank Protection and Control System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...8 18 C70 Capacitor Bank Protection and Control System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 414: ...9 18 C70 Capacitor Bank Protection and Control System GE Multilin 9 1 OVERVIEW 9 THEORY OF OPERATION 9 ...
Страница 436: ...10 22 C70 Capacitor Bank Protection and Control System GE Multilin 10 4 SETTING EXAMPLE 10 APPLICATION OF SETTINGS 10 ...
Страница 547: ...GE Multilin C70 Capacitor Bank Protection and Control System B 79 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 548: ...B 80 C70 Capacitor Bank Protection and Control System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Страница 598: ...E 12 C70 Capacitor Bank Protection and Control System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...