GE Multilin
C70 Capacitor Bank Protection and Control System
B-41
APPENDIX B
B.4 MEMORY MAPPING
B
9E4C
Voltage differential 1 stage 3A pickup
0.001 to 1.000
pu
0.001
F001
30
9E4D
Voltage differential 1 stage 4A pickup
0.001 to 1.000
pu
0.001
F001
40
9E4E
Voltage differential 1 stage 1B pickup
0.001 to 1.000
pu
0.001
F001
10
9E5F
Voltage differential 1 stage 2B pickup
0.001 to 1.000
pu
0.001
F001
20
9E50
Voltage differential 1 stage 3B pickup
0.001 to 1.000
pu
0.001
F001
30
9E51
Voltage differential 1 stage 4B pickup
0.001 to 1.000
pu
0.001
F001
40
9E52
Voltage differential 1 stage 1C pickup
0.001 to 1.000
pu
0.001
F001
10
9E53
Voltage differential 1 stage 2C pickup
0.001 to 1.000
pu
0.001
F001
20
9E54
Voltage differential 1 stage 3C pickup
0.001 to 1.000
pu
0.001
F001
30
9E55
Voltage differential 1 stage 4C pickup
0.001 to 1.000
pu
0.001
F001
40
9E56
Voltage differential 1 stage 1 pickup delay
0 to 600.00
s
0.01
F001
3000
9E57
Voltage differential 1 stage 2 pickup delay
0 to 600.00
s
0.01
F001
1000
9E58
Voltage differential 1 stage 3 pickup delay
0 to 600.00
s
0.01
F001
100
9E59
Voltage differential 1 stage 4 pickup delay
0 to 600.00
s
0.01
F001
20
9E5A
Voltage differential 1 dropout delay
0 to 600.00
s
0.01
F001
25
9E5B
Voltage differential 1 stage 1 block
0 to 65.535
---
1
F300
0
9E5C
Voltage differential 1 stage 2 block
0 to 65.535
---
1
F300
0
9E5D
Voltage differential 1 stage 3 block
0 to 65.535
---
1
F300
0
9E5E
Voltage differential 1 stage 4 block
0 to 65.535
---
1
F300
0
9E5F
Voltage differential 1 target
0 to 2
---
1
F109
0 (Self-Reset)
9E60
Voltage differential 1 events
0 to 1
---
1
F102
0 (Disabled)
9E61
...Repeated for voltage differential 2
9E82
...Repeated for voltage differential 3
VT Fuse Failure (Read/Write Setting) (6 modules)
A040
VT Fuse Failure Function
0 to 1
---
1
F102
0 (Disabled)
A041
...Repeated for module number 2
A042
...Repeated for module number 3
A043
...Repeated for module number 4
A044
...Repeated for module number 5
A045
...Repeated for module number 6
Selector switch actual values (read only)
A210
Selector switch 1 position
1 to 7
---
1
F001
0
A211
Selector switch 2 position
1 to 7
---
1
F001
1
Selector switch settings (read/write, 2 modules)
A280
Selector 1 Function
0 to 1
---
1
F102
0 (Disabled)
A281
Selector 1 Range
1 to 7
---
1
F001
7
A282
Selector 1 Timeout
3 to 60
s
0.1
F001
50
A283
Selector 1 Step Up
0 to 65535
---
1
F300
0
A284
Selector 1 Step Mode
0 to 1
---
1
F083
0 (Time-out)
A285
Selector 1 Acknowledge
0 to 65535
---
1
F300
0
A286
Selector 1 Bit0
0 to 65535
---
1
F300
0
A287
Selector 1 Bit1
0 to 65535
---
1
F300
0
A288
Selector 1 Bit2
0 to 65535
---
1
F300
0
A289
Selector 1 Bit Mode
0 to 1
---
1
F083
0 (Time-out)
A28A
Selector 1 Bit Acknowledge
0 to 65535
---
1
F300
0
A28B
Selector 1 Power Up Mode
0 to 2
---
1
F084
0 (Restore)
A28C
Selector 1 Target
0 to 2
---
1
F109
0 (Self-reset)
A28D
Selector 1 Events
0 to 1
---
1
F102
0 (Disabled)
A28E
Reserved (10 items)
---
---
1
F001
0
A298
...Repeated for Selector 2
DNP/IEC Points (Read/Write Setting)
A300
DNP/IEC 60870-5-104 Binary Input Points (256 items)
0 to 65535
---
1
F300
0
A400
DNP/IEC 60870-5-104 Analog Input Points (256 items)
0 to 65535
---
1
F300
0
Table B–9: MODBUS MEMORY MAP (Sheet 34 of 53)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание UR Series C70
Страница 2: ......
Страница 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C70 Capacitor Bank Protection and Control System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 124: ...4 30 C70 Capacitor Bank Protection and Control System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...8 18 C70 Capacitor Bank Protection and Control System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 414: ...9 18 C70 Capacitor Bank Protection and Control System GE Multilin 9 1 OVERVIEW 9 THEORY OF OPERATION 9 ...
Страница 436: ...10 22 C70 Capacitor Bank Protection and Control System GE Multilin 10 4 SETTING EXAMPLE 10 APPLICATION OF SETTINGS 10 ...
Страница 547: ...GE Multilin C70 Capacitor Bank Protection and Control System B 79 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 548: ...B 80 C70 Capacitor Bank Protection and Control System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Страница 598: ...E 12 C70 Capacitor Bank Protection and Control System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...