EM, feedback circuit-
monitoring
351
02/16 MN05013001Z EN
Parameters
When using the function block in the circuit diagram for the
first time, use OK to automatically enter the general display
of function block parameters, as shown in the figure on the
left. Enter the function block settings here. The display
contains the following elements:
The parameters consist of the following:
Enable
The Enable parameter specifies whether an external function
block enable is required. Further information can be found at
section “Enable parameter, EN enable coil” on page 345.
This parameter is factory set to NEN, the function block is
active without an external enable.
EM01 NEN MST *
*** ***
>FT
3.0s
EM01
Function block: external device monitoring , No. 1
NEN
Enable: None required
MST
Operating mode: Manual start
>FT
Monitoring time: 3.0 seconds
Mode
parameter
Function, parameterisation in the func-
tion block
EN
External enable required
NEN
No external enable required