ySafety internal
628
02/16 MN05013001Z EN
The operation on the non-safety easyNet is described in
chapter “Introduction to the ea
yNet network”, starting
How is an expansion device detected?
If at least one
R
contact or contact/coil
S
is used in the circuit
diagram, the basic unit assumes that an expansion unit is
connected.
Transfer behaviour
The input and output data of the expansion units is trans-
ferred serially in both directions.
Reaction times of the inputs/outputs of the expan-
sion devices
The debounce setting has no effect on the expansion unit.
Transfer times for input and output signals:
• Local expansion
– Time for inputs R1 to R12: 30 ms + 1 cycle.
– Time for outputs S1 to S6 (S8): 15 ms + 1 cycle.
• Remote expansion
– Time for inputs R1 to R12: 80 ms + 1 cycle.
– Time for outputs S1 to S6 (S8): 40 ms + 1 cycle.
For an approximate cycle time, you can use the circuit
diagram processing time divided in half,