Safety function blocks
468
02/16 MN05013001Z EN
The factory setting of this parameter is MST, Manual Start.
Startup test
The safety gates must be opened explicitly for the startup
test. The startup test is carried out
• with every STOP-RUN change of easySafety or after
• each deactivation and subsequent activation of the func-
tion block via the function block coil EN.
With MST or CST mode, the Reset coil must be activated
afterwards. The startup test is further described in section
“Parameter SUT (Startup test)” on page 347.
The factory setting of this parameter is OFF.
Parameters
Function, parameterisation in the func-
tion block
MST
Manual start
CST
Controlled start
AST
Automatic start, no manual restart
Parameters
Function, parameterisation in the func-
tion block
OFF
No startup test required
SUT
The startup test must be carried out
h
If you are using the SG (safety gate) function block in the
operating mode 1L or 2L (with guard locking monitoring)
the startup test (SUT parameter) is not possible.