EN, enable switch
367
02/16 MN05013001Z EN
Example
Monitoring of an enable switch with cross-circuit monitoring
of the external wiring. Activation coil EN01SA is triggered by
a key switch. The enable switch must only be active at
reduced speed. This condition is scanned with the OM
(maximum speed monitoring) function block. The wiring of
the OM function block is described in section “OM,
Maximum speed monitoring” on page 434.
Moving the switch from position 0 to 1 triggers the enable.
The enable contact EN01QS of the function block closes and
the signal is assigned to the safety marker MS05 for further
processing.
The enable is removed if the switch is held down in
position 2 or released and is thus returned to position 0.
When returning to switch position 0 from switch position 2,
there is no enable when passing through position 1.
The guard can only be bridged for up to 3 minutes.