Safety function blocks
438
02/16 MN05013001Z EN
Maximum rotation frequency
The maximum permissible rotation frequency FR is the
frequency that the motor must not exceed. The setpoint for
this frequency is entered as parameter >FR, the actual value
is determined via the two encoders on the motor.
Parameters
Function, parameterisation in the func-
tion block
>FR
50 - 1000 Hz; adjustable in increments of
g
1 Hz
(default setting = 50 Hz)
i
Warning!
The highest permissible rotating frequency at device
inputs IS1 and IS2 is 1000 Hz.
Higher frequencies are not reliably detected by the
easySafety device and can cause malfunction.
It is the engineer’s responsibility to ensure that no higher
rotary frequencies can be applied at IS1 and IS2.