Activating/deactivating
DEBOUNCE
589
02/16 MN05013001Z EN
Activating/deactivating
DEBOUNCE
The easySafety device is factory set to evaluate input signals
with an input delay, the so-called DEBOUNCE function. This
ensures that any contact bouncing of switches and pushbut-
tons is masked out.
However, for many applications, it is necessary to evaluate
very short input signals. In this case, it is possible to deacti-
vate the debounce for each input individually as required.
X
Press DEL and ALT to call up the System menu.
X
Change to the system menu via STD PARAMETERS and
choose the DEBOUNCE menu item.
Activating DEBOUNCE
X
To activate
DEBOUNCE
, choose
DEBOUNCE
and press
OK
.
The menu for selective debounce settings opens in which
you can activate or deactivate the debounce for each indi-
vidual input.
X
Use the cursor buttons
Í
or
Ú
to select the required
DEBOUNCE setting and press OK
.
The debounce is activated.
X
Press ESC to return to the previous menu.
h
If the easySafety device is protected with an STD PASS-
WORD, you must remove password protection before you
can call the system menu.
P BUTTONS
Æ
RUN MODE
DEBOUNCE..
DISPLAY
æ
DEBOUN. ALL ON
Æ
DEBOUN. ALL OFF
å
IS01
IS02
æ
h
Caution!
Debounced inputs may not be used in the safety circuit
diagram.