Safety function blocks
380
02/16 MN05013001Z EN
The circuit diagram in easySafety has five rungs:
Figure 189:
Emergency-stop example: Circuit diagram in
easySafety
The ES01I1 and ES01I2 input coils are directly associated
with the device terminals IS9 and IS10 and the Reset coil
ES01RE is linked to IS13. The ES01QS enable contact
switches the device outputs QS1 and QS3 directly.
The enable parameter stays at NEN, i.e. no external enable.
The operating mode is changed to CST “Controlled Start”.
The evaluation of the emergency-stop button stays set to 2-
channel operation (2CH) and the discrepancy time to 0.5
seconds.
The test signals for cross-circuit monitoring are assigned to
the corresponding device inputs in the TEST SIGNALSmenu.
IS09---------------------------
Ä
ES01I1
IS10---------------------------
Ä
ES01I2
IS13---------------------------
Ä
ES01RE
ES01QS------------------------
uÄ
QS01
hÄ
QS03
ES01 NEN CST *
*** 2CH
>DT
0.5s
DG:
IS01 <- -
Æ
...
IS09 <- T3
IS10 <- T4 *
æ
...
IS13 <- T4 *
IS14 <- -