Installation
66
02/16 MN05013001Z EN
Cable length with cross-sections
For correct operation of the easyNet network the cable
lengths, cross-sections and cable resistances must match
those listed in the following table.
The impedance of the cables used must be 120
O
.
The maximum transmission speed depends on the total
length of the network cables,
Cable length
Cable resistance
Cross-section
m
m
O
/m
mm
2
AWG
up to 40
F
140
0.13
26
up to 175
F
70
0.25 to 0.34
23, 22
up to 250
F
60
0.34 to 0.50
22, 21, 20
up to 400
F
40
0.5 to 0.6
20, 19
up to 600
F
26
0.75 to 0.8
18
up to 1000
F
16
1.5
16
h
The installation of an expensive fibre optic link is
recommended with cable lengths > 500 m.