LC, light curtain
403
02/16 MN05013001Z EN
The circuit diagram in easySafety only has three rungs:
Figure 203:
Example 1 "light curtain": Circuit diagram in
easySafety
The LC01I1 and LC01I2 input coils of the function block are
directly associated with the device terminals IS2 and IS3, and
the LC01QS enable contact switches the device output QS1.
The enable parameter stays in the default setting. The oper-
ating mode is changed to AST “Automatic Start”. The SUT
startup test is also activated.
The signal diagram for this application shows the depend-
ence of the enable contact LC01QS on the status of coils
LC01I1 and LC01I2:
Figure 204:
Example 1 Light curtain: signal diagram
a
Light curtain free but startup test not yet completed
b
Intervention, light curtain interrupted
c
Enable after leaving hazardous zone
d
Light curtain interrupted, enable removed
e
Light curtain clear, automatic enable via LC01QS
IS02---------------------------
Ä
LC01I1
IS03---------------------------
Ä
LC01I2
LC01QS-------------------------
Ä
QS01
LC01 NEN AST *
SUT ***
>DT
1.0s
LC01I1
LC01QS
LC01ER
LC01I2
a
b
c
d
e