LM, light curtain muting
417
02/16 MN05013001Z EN
Tabelle 16: Diagnostics-/-Error codes
More information on the diagnostics output DG: is provided
in section “Common features”, page 348.
Status number
Plain text
Hexadecimal (0–F)
decimal (0-9)
0000
0000
No Enable.
2001
8193
Enable issued; waiting for first (or only) input.
2002
8194
Waiting for second input.
2003
8195
Waiting for rising edge at Reset.
2004
8196
Waiting for falling edge at Reset.
2005
8197
Only one channel has been opened.
200E
8206
Waiting for inputs during startup testing.
8006
32774
Light curtain free (QS = 1).
8011 - 8037
32785 - 32823
States within the muting sequence:
The flow sequence of the safety function block's muting
states depends on the input signals and the muting
procedure. The current states within the muting
sequence can be evaluated based on the diagnostic
codes.
8018
32792
Muting state Move Clear.
F001
61441
Error: Discrepancy time expired.
F003
61443
Error: Muting duration exceeded.
F004
61444
Error: Synchronization duration exceeded.
F005
61445
Error: Clearing duration exceeded.
F00B
61451
Error: Reset and inputs operated on function block
startup.
F00E
61454
Error: Only one channel was opened and closed.
F019
61465
Error: Implausible processing sequence.
F01A
61466
Error: Muting sequence completed, light curtain not free.
F01B
61467
Error: Clearing completed; light curtain or sensors not
free.