Commissioning NET stations
551
02/16 MN05013001Z EN
Setting the NET ID of a NET operand
Requirement: You must have selected an I.., R.., Q.., R.., RN..
S.. or SN.. operand in the standard circuit diagram and Entry
mode must have been selected.
This mode is displayed by a flashing operand.
X
Use the cursor buttons
ú
to move the cursor to the position
to the left of the operand. A flashing zero appears as the
initial value.
Enter the cursor buttons
Í
or
Ú
to define the required NET
ID; in this case NET ID 7.
Confirm the entry with the OK button.
The local I.., R.., Q.. or S.. operand has been changed to a
NET operand nI.., nR.., nQ.. and nS...
The following figure shows how the IS../QS. inputs/outputs
of an easySafety device are assigned to the nI.. and nQ.. NET
operands.
Table 28: Reading inputs/outputs IS../QS. of a easySafety device in
the standard circuit diagram of another station via the
NET (see also figure 283)
I 01
L: 1 C:1 B:7732
7I 01
L: 1 C:1 B:7732
Input in the
standard
circuit
diagram
easySafety
input with
NET ID n
Output in the
standard
circuit
diagram
easySafety
output with
NET ID n
nI
IS
nQ
QS/QR
n I 1
q
IS1
n Q 1
q
QS1
…
…
…
…
n I 14
q
IS14
n Q 4
q
QS4
n Q 7
q
QR1
j
Danger!
The safety inputs and outputs of an easySafety device
operating as a NET station can be read in the standard
circuit diagram of another NET station, however, they lose
their safety properties.