Introduction to the ea
s
yNet
network
523
02/16 MN05013001Z EN
The physically first NET station that is located at the
beginning of the network manages the network and
therefore the configuration, commissioning and diagnostics
of the NET. This station with NET ID 1 is given the most
extensive write/read access within the network.
In this way, the commissioning of NET stations is very simple.
Apart from the installation with prefabricated cables, this
only requires the following for the standard loop through
topology:
• Definition of the first NET station by assigning NET ID 1
and the possible necessary modification of the baud rate
in the NET PARAMETERS menu.
• Creation of the station list with automatic assignment of
the NET IDs for the connected devices in the STATION
menu.
• Configuration via the CONFIGURATION menu.
Further information on the configuration of the NET can be
found on page 536.
Commissioning is even simpler with easySoft-Safety and
easySoft-Pro. From easySoft-Pro version V6.30 Pro you can
create NET configurations that contain easySafety devices
from the ES4P device family in addition to previously
established devices. This easySoft-Pro software covers all
easySafety device versions under the heading ES4P device.
Further information on this is provided in the Online Help of
easySoft-Pro.
h
The complete configuration of the ES4P device can only be
carried out with easySoft-Safety. However, easySoft-Pro
allows you to transfer NET settings for commissioning
such as "NET-ID", the baud rate and "Bus-Delay" to the
easySafety device. This may be necessary in order to also
address the other devices and test their functions.