ySafety internal
624
02/16 MN05013001Z EN
Table 32:
Behaviour of
easySafety
after an error
Error
class
Behaviour of the device in the event of a fault
Acknowl-
edgement
Fault occurs in
STOP mode
STOP/
RUN
change-
over
possible?
Fault occurs in RUN mode
C
(minor)
LED FAULT continu-
ously lit green
yes
• LED FAULT flashes green (0.5
Hz)
• Safety circuit diagram in RUN
• Standard circuit diagram in
RUN
• All device outputs are
switched.
• Output via diagnostics contact
ID.., e.g. ID14 = 1 for an
easyLink error.
• Flashing on the Status display.
Automatic
error
acknowl-
edgement
after rectifi-
cation.
B
(serious)
• LED FAULT contin-
uously lit orange
• Fault indication
visible on display
• Local device
outputs are
switched off
no
• LED FAULT flashes orange
(flash frequency 0.5 Hz).
• Safety circuit diagram stopped
• Standard circuit diagram in
RUN
• All device outputs are switched
off.
• Output at the diagnostics
contact IG (ID10 = 1).
• Fault indication visible on
display
Error
acknowl-
edgement by
switching
from STOP to
RUN. If
necessary
the power
supply must
be switched
off/on.
A (fatal)
• LED FAULT contin-
uously lit red
• Fault indication
visible on display
• Local device
outputs are
switched off
no
• LED FAULT continuously lit red
• Safety circuit diagram stopped
• Standard circuit diagram
stopped
• All device outputs are switched
off.
• Fault indication visible on
display
Error
acknowl-
edgement is
not possible.
Device is
faulty.