![Eaton easySafety Скачать руководство пользователя страница 377](http://html1.mh-extra.com/html/eaton/easysafety/easysafety_manual_3958374377.webp)
ES, Emergency-stop
373
02/16 MN05013001Z EN
Parameters
When using the function block in the circuit diagram for the
first time, use OK to automatically enter the general display
of function block parameters, as shown in the figure on the
left. Enter the function block settings here. The display
contains the following elements:
The parameters consist of the following:
Enable
The enable parameter allows the use of the enable coil for
activation or deactivation. Further information can be found
at section “Enable parameter, EN enable coil” on page 345.
This parameter is factory set to NEN, the function block is
active without an external enable.
ES01 NEN MST *
*** 2CH
>DT
3.0s
ES01
Function block: emergency-stop no. 01
NEN
Enable: None required
MST
Operating mode: Manual start
2CH
Evaluation: 2-channel emergency-stop circuit
>DT
Discrepancy time: 3.0 seconds
Parameters
Function, parameterisation in the func-
tion block
EN
External enable required
NEN
No external enable required
Содержание easySafety
Страница 1: ...Manual Control relay suitable for safety circuits Safety ES4P 02 16 MN05013001Z EN ...
Страница 4: ...2 ...
Страница 42: ...38 02 16 MN05013001Z EN ...
Страница 80: ...Installation 76 02 16 MN05013001Z EN ...
Страница 112: ...108 02 16 MN05013001Z EN ...
Страница 606: ...602 02 16 MN05013001Z EN ...