LM, light curtain muting
413
02/16 MN05013001Z EN
Operating mode
After easySafety has determined the conditions for safe
operation, there are different kinds of restarts possible. They
are described in greater detail as operating modes in section
“Operating mode parameter, RE reset coil” on page 346.
The factory setting of this parameter is MST, Manual Start.
Startup test
The protected area must be explicitly interrupted for the
startup test and the Reset command initiated. The startup
test is further described in section “Parameter SUT (Startup
test)” on page 347.
Parameters
Function, parameterisation in the func-
tion block
AST
Automatic start, no manual restart
MST
Manual start
CST
Controlled start
Parameters
Function, parameterisation in the func-
tion block
OFF
No startup test required
(default setting)
SUT
The startup test must be carried out
Содержание easySafety
Страница 1: ...Manual Control relay suitable for safety circuits Safety ES4P 02 16 MN05013001Z EN ...
Страница 4: ...2 ...
Страница 42: ...38 02 16 MN05013001Z EN ...
Страница 80: ...Installation 76 02 16 MN05013001Z EN ...
Страница 112: ...108 02 16 MN05013001Z EN ...
Страница 606: ...602 02 16 MN05013001Z EN ...