Rules in the safety circuit
diagram
343
02/16 MN05013001Z EN
the safety circuit diagram is no longer available in the
standard circuit diagram and vice versa.
• Rule 10:
Use the safety device outputs QR and QS only once as a
coil in the safety circuit diagram.
• Rule 11:
When using an OM and/or ZM function block you must not
use the device inputs IS1 and IS2 as contacts in the circuit
diagram.
• Rule 12:
If you wish to implement an external function block enable
(function block parameter set to EN), you must wire the EN
coil of the function block in the safety or standard circuit
diagram.
• Rule 13:
If you are using a safety function block in the safety circuit
diagram, its QS output must be wired as a contact.
• Rule 14:
Currently not defined.
• Rule 15:
If the Manual Start operating mode (MST) or Controlled
Start mode (CST) is set, you must wire the RE coil of the
function block concerned (e.g. ES01RE) as a coil.
• Rule 17:
If you have set the multi-channel capability, all channels of
the function block must be addressed as coils. Example of
emergency-stop function block: Parameter 2CH requires
the wiring of both function block channels ES01I1 and
ES01I2. All the necessary coils must be wired for a func-
tion block. For example, a light curtain is always 2-
channel. You must also wire the coil I1 and I2 of the LC
light curtain function block, see figure below:
• Rules 18 and 19:
Currently not defined.
IS05---------------------------
Ä
LC01I1
IS06---------------------------
Ä
LC01I2