Standard function blocks
208
02/16 MN05013001Z EN
Example 4
: Copying of marker bytes, destination range
violation error
Marker range MB81 to MB96 is to be transferred to MD93
to MD96. The length is 16 bytes.
• Parameters of function block BT01:
– Source range:
>I1 MB81
– Destination range: >I2 MD93
– Number of bytes:
>NO 18
The error message “Number of elements exceeds the
destination range” is output.
BT01E1 is 1.
Example 5
: Comparison of marker blocks, range overlap
error
12 bytes are to be copied starting from MW60. MW64 is
specified as destination address.
• Parameters of function block BT01:
– Source range:
>I1 MW60
– Destination range: >I2 MW64
– Number of bytes:
>NO 12
The error message “Both ranges overlap” is output.
BT01E2 is 1.
h
The transfer is in byte format. MD93 to MD96 is 16 bytes.
18 bytes were incorrectly defined as length.
h
The copy operation is in byte format. MW60 to MW64 is 8
bytes. The number of bytes is 12 bytes.