Sources
parameter - EKmin minimum temperature
The parameter is intended to set the minimum operating temperature of the external boiler (EK
switching temperature). However, the actual EK temperature corresponds to the requirements of
the heating circuits and the DHW heating circuit.
Factory default setting: 80 °C
INFO
- P04
Sources
, P05
Sources
, P06
Sources
, P07
Sources
, P08
Sources
a P16
Sources
parameters are visible
only after the activation of the EKx external boiler function.
• P06
Sources
parameter - EKdif shutdown difference
The parameter is intended to set the shutdown difference of the external EK boiler (EK shutdown
= EKmin (required EK temperature ) + EKdif). The actual EK temperature corresponds to the
requirements of the heating circuits and the DHW heating circuit.
Factory default setting: 3 K
INFO
- P04
Sources
, P05
Sources
, P06
Sources
, P07
Sources
, P08
Sources
a P16
Sources
parameters are visible
only after the activation of the EKx external boiler function.
• P07
Sources
parameter - EKmax maximum temperature
The parameter is intended to set the maximum operating temperature of the EK external boiler.
At the same time, it is the temperature, at which the function given by
→
P16
Sources
parameter
- Enforced losses EK is activated.
Factory default setting: 95 °C
INFO
- P04
Sources
, P05
Sources
, P06
Sources
, P07
Sources
, P08
Sources
a P16
Sources
parameters are visible
only after the activation of the EKx external boiler function.
• P08
Sources
parameter - DHW summer heating using EK
The parameter is used to switch on (enable) the DHW tank heating in summer mode by the EK
external boiler.
Factory default setting: Off
INFO
- P04
Sources
, P05
Sources
, P06
Sources
, P07
Sources
, P08
Sources
a P16
Sources
parameters are visible
only after the activation of the EKx external boiler function.
10. Setting menu - Sources
Содержание ACD 03
Страница 1: ...Operation manual EN www atmos eu EN 1 ACD03 04 Operation manual ...
Страница 2: ...Operation manual EN www atmos eu ACD03 04 ...
Страница 8: ...Operation manual EN www atmos eu EN 8 ACD03 04 ...
Страница 265: ...Operation manual EN www atmos eu EN 265 ACD03 04 12 Overview of menus and their parameters ...