10. Setting menu - Hydraulics
/F
unction configuration/Heating circuit 1 function
MKP1
–
pump of mixed (heating) circuit 1
(except for RLA circuit).
MK1O
–
actuator of mixed (heating) circuit 1
- opening phase of actuator of mixed (heating)
circuit 1 (except DK type).
MK1C
–
actuator of mixed (heating) circuit 1
- closing phase of actuator of mixed (heating)
circuit 1 (except DK type).
ATTENTION
- For the circuit to function properly, specific terminals must be assigned to
the sensor (VF1), the pump (MKP1) and the three-way valve actuator (MK1O and MK1C).
An inactivated function (unassigned terminal) is displayed with the
!
warning sign.
M
B
A
MK1C
MK1O
VF1
AF (4)
WF (5)
ATMOS
ACD
2 - 6 bar
10 – 15 °C
ARU5
DKP (59)
MKP1
ATMOS
INFO
- If necessary, the actuator direction of rotation can be easily reversed without the need
for physical re-wiring of the actuator (terminals). To change the rotation direction, go to
→
Hydraulics/Function configuration/Actuator direction of rotation. More information
in Menu - Actuator direction of rotation.
Additional functions can be defined in the Heating circuit 1 function submenu: