Operation manual - EN
www.atmos.eu
EN - 231
ACD03/04
• P25
Heating circuit
parameter - Holiday mode operation
The parameter is used to set the type of operation in
Holiday
mode for mixed circuits of
MK, DK type
Factory default setting:
STBY
Setting options:
ECO
– operation as in the
Setback
mode - heating to attenuation (moon ) temperature
STBY
– operation as in the
Standby
mode - heating to antifreeze room temperature accor-
ding to
→
P08
Heating circuit
parameter
• P26
Heating circuit
parameter - Flow temperature dynamic protection
The parameter is intended to activate a special function that ensures that the temperature of the
water flowing into the mixed circuit is always lower by 4 K than the boiler (source) temperature
(WF), storage tank temperature (PF) or external boiler temperature (EKF).
The function is active for mixed circuits: MK, KR, FR and RLA type.
Factory default setting:
2 - according to WF, PF, EKF
Setting options:
1
– off
2
– according to WF, PF, EKF
INFO -
it is a protection against unnecessary mixing of boiler (source) and accumulation
tank (against energy degradation).
10. Setting menu - Heating circuit 1 / 2 / 3 / (4)