Operation manual - EN
www.atmos.eu
EN - 203
ACD03/04
• P09
Boiler
parameter - FAN, PRESS ventilation time
The parameter is intended for setting the ventilation time, i.e. the time required to start the boiler
exhaust fan (FAN) (switching off the pressure fan - PRESS) when stoking fuel, removing ash or
cleaning the boiler.
To start the ventilation time, if the fan (FAN) is off, (PRESS) is on, click on the
button (hand).
Factory default setting: 3,0 min
INFO
- After the set time, the controller returns to its original status.
• P10
Boiler
parameter - Maximum flue gas temperature for FAN
The parameter is intended for boilers with manual stoking to set the maximum flue gas tempera-
ture, as protection of the flue gas sensor, or some parts of the boiler against damage.
Factory default setting: 400 °C
INFO
- When the maximum flue gas temperature is exceeded, the FAN (PRESS) output is
switched off.
• Parameter P11
Boiler
– Flue gas temperature for SEKGS servo flap
The parameter is intended for setting the flue gas limit temperature, at which selected models of
boilers (equipped with air flap with actuator DCxxGSE, DCxxGSP) will be controlled to close the
inlet of combustion air to the boiler.
Factory default setting: 180 °C
INFO
- This is a function to preserve high boiler efficiency in different modes of operation.
CAUTION
- For
DCxxGSE
boiler models, the output is
switched on
when the flue gas
temperature is exceeded.
- For
DCxxGSP
boiler models, the output is
shut down
when the flue gas temperature is
exceeded.
10. Setting menu - Boiler
Содержание ACD 03
Страница 1: ...Operation manual EN www atmos eu EN 1 ACD03 04 Operation manual ...
Страница 2: ...Operation manual EN www atmos eu ACD03 04 ...
Страница 8: ...Operation manual EN www atmos eu EN 8 ACD03 04 ...
Страница 265: ...Operation manual EN www atmos eu EN 265 ACD03 04 12 Overview of menus and their parameters ...