Operation manual - EN
www.atmos.eu
EN - 15
ACD03/04
Recommended sensors installation
WF boiler temperature sensor in the boiler pocket, the sensor is added to other capillaries from the
thermostats and thermometer of the original electromechanical regulation of the boiler.
The sensor must be placed as far (deep) as possible in the boiler pocket for accurate temperature
sensing!!!
The AGF flue gas sensor attached to the boiler flue gas duct (DCxxS, DCxxSX, DCxxGS, CxxS(T)),
the sensor is added to the flue gas thermostat capillary of the original electromechanical regulation
of the boiler.
This sensor must be covered with insulation!!!
The AGF flue gas sensor attached to the boiler flue gas duct with tube heat exchanger (DCxxGSE,
DCxxGSX, DCxxDG), the sensor is added to the flue gas thermostat capillary of the original
electromechanical regulation of the boiler.
This sensor must be covered with insulation!!!