Operation manual - EN
www.atmos.eu
EN - 201
ACD03/04
• P03
Boiler
parameter - KTmax maximum boiler operating temperature
The parameter is used to set the maximum operating temperature of the boiler measured by the
WF sensor.
If the maximum operating temperature of the boiler is exceeded, the protection of the boiler against
overheating is activated (
→
P16
Boiler
parameter Enforced boiler losses - On).
When connected
without the accumulation
tank, the boiler is cooled by conducting excess ener-
gy into the heating circuits and the DHW tank.
When connected
with the accumulation
tank, the energy is conducted into the accumulation tank
until the Maximum operating temperature of the accumulation tank PFmax, defined by
→
P02
Accumulation tank
parameter, is reached. After exceeding the PFmax temperature of the boiler, excess
energy is conducted to the heating circuits and the DHW tank.
Factory default setting: 95 °C
Recommended setting:
Boilers without accumulation tank - 95 °C
Boilers with accumulation tank - 95 °C
INFO
- When heating to a higher temperature is required, it is necessary to think about the
setting of the boiler safety thermostat and the opening temperature of the cooling loop valve.
• P04
Boiler
-parameter - DKP switching temperature of boiler pump
The parameter is used to set the temperature at which the DKP pump in the boiler circuit is
switched on.
Factory setting
in hydraulic diagrams
with accumulation tank: 30 °C
Factory setting
in hydraulic diagrams
without accumulation tank: 70 °C
CAUTION
- The condition of correct operation of the boiler circuit is the connection of
the boiler with the boiler protection device against lowtemperature corrosion (Laddomat,
thermoregulation valve, controlled return (RLA)).
INFO
- When connecting the boiler with RLA controlled return, the DKP switching tempe-
rature of the boiler pump should not be higher than the set temperature of the return water
to the boiler in
→
P11
Heating circuit
parameter.
• P05
Boiler
parameter - DKP shutdown difference
The parameter is used to set the DKP shutdown difference of the pump in the boiler circuit.
Factory default setting: 2 K
10. Setting menu - Boiler