Operation manual - EN
www.atmos.eu
EN - 92
ACD03/04
PRESS
–
pressure boiler fan
The fan is operated by the button (hand) on the controller display. When the boileris cold,
start the fan for firing up by pressing the button with the (hand) symbol.
The time for
firing up the boiler
with manual stoking is factory-set to a maximum of 60
minutes (P08
Boiler
parameter). The controller remains in
firing up
mode until it reaches the
minimum flue gas temperature defined in P18
Boiler
parameter. If the
minimum flue gas
temperature
is not reached, the boiler (fan) will be shut down.
During boiler operation, the fan is controlled automatically according to the water
temperature (WF sensors) set in the Boiler menu. When the temperature defined by P02
Boiler
parameter is reached, the fan is switched off, when the boiler water temperature drops by
the difference defined by P06
Boiler
parameter, it is switched on again.
When all fuel is burnt out (the flue gas temperature - lower than P18
Boiler
parameter), the fan
(boiler circuit pump - according to P17
Boiler
parameter setting) is shut down.
INFO
- Always
stop
the
pressure
boiler
fan
before
opening
the door (e.g. when stoking)
with the (hand) button for the time specified by P09
Boiler
parameter.
BRE
–
automatic boiler with burner
(for pellets/fuel oil). The boiler operates in automatic
mode according to the defined logic (WF boiler water temperature, PF and FPF accumulation
tanks, as required by the heating system).
The boiler can be switched off by pressing the
button on the controller display
, e.g. to be cleaned.
For automatic boilers with BRE function, additional functions can be activated:
- BRS
– external control (switch on/switch off) of the boiler by the controller, GSM
gateway, pressure sensor of the heating system, CO alarm, etc., via the terminal of one
of the free inputs (except DVI1 or DVI2)
- BRSH
– the same function as BRS using DVI1 or DVI2 terminals (voltage input
230V)
INFO
- The logic of the burner control according to the sensors in the PF accumulation tank
(upper) and FPF accumulation tank (lower) is the same as for the ATMOS pellet burners, the
control according to the TV sensor (upper) and TS sensor (lower). The temperature is not set
up, it is automatically calculated according to the requirements of the heating system. Only
the minimum required temperature can be set, which is defined by P18
Accumulation tank
parameter.
SEKGS
–
Belimo servo flap
on the combustion air supply to the DCxxGSE, DCxxGSP boiler
controlled by AGF flue gas temperature
BREO – output of the turned on boiler
(230 V) - e.g. boiler operating hours counter, monitoring
of controlled boiler operation, signal for fuel supply (external pellet feeder), etc.
When the condition of burner operation is met, the output is switched on.
10. Setting menu - Hydraulics
/F
unction configuration/Boiler