• P14
Accumulation tank
parameter - Minimal tank requirement value
The parameter is used to set the minimum temperature on the tank, which the boiler must reach in
order to turn off the BRE burner (for pellets) or the electric coil in the EHP tank (electric heating).
When using one PF sensor or when using two PF (upper) and FPF (lower) sensors, the required
temperature must be reached on all sensors in the tank after switching on the heat source (boiler).
Factory default setting: 70 °C
• P15
Accumulation tank
parameter - Shutdown difference of the DKP protection during charging
The parameter is used to set the shutdown difference of the pump in the DKP boiler circuit, when
connected with the accumulation tank (
→
P10
Accumulation tank
parameter =
1 - accumulation
).
The DKP pump is switched off if the WF boiler temperature is lower by the shutdown difference
than the temperature in the PF accumulation tank (WF<PF+difference).
Factory default setting: -3 K
• P16
Accumulation tank
parameter - Switching difference of the DKP protection during charging
The parameter is used to set the switching difference of the pump in the DKP boiler circuit when
connected with the accumulation tank (
→
P10
Accumulation tank
parameter =
1 - accumulation
).
Switching on (starting) the DKP pump occurs if the temperature of the WF boiler is higher by the
switching difference than the temperature in the PF accumulation tank (WF≥PF+difference).
10. Setting menu - A
ccumulation tank