Operation manual - EN
www.atmos.eu
EN - 193
ACD03/04
In case of setting P07
Syste
m parameter to
Off
, all time blocks for comfortable temperatures have the
same value that corresponds to the comfort temperature set under the button.
The setback temperature requirement (gaps between individual comfort blocks) corresponds to
the temperature set under the button.
• P08
System
parameter - Fixed outdoor temperature
The parameter value (temperature) is automatically applied when the outdoor AF sensor is
damaged or deactivated.
• P09
System
parameter - Climate zone
It is a parameter of the average lowest outdoor (calculated) temperature that can be expected at the
place of installation of the controller. In practice, this value is used as the basis for the design of
the heating system and the calculation of the power of the heating source. The parameter defines
the top point of the heating curve.
Factory default setting:
-12 °C
• P10
System
parameter- Building type
The rate of change of room temperature depending on the change of outdoor temperature affects
the maintenance of thermal comfort in the building. This is influenced by the properties of the
material, the building is constructed from. For this reason, the average outdoor temperature is used
to calculate the current thermal demand.
The optimal averaging of the outdoor temperature is determined by the type of building:
1 - light
– construction with low temperature inertia, where there are rapid changes in room
temperature, for example, a wooden structure.
Outdoor temperature averaging time -
2 hours.
2 – medium
– standard brick building with standard insulation.
Outdoor temperature averaging timey -
8 hours.
3 – heavy
– brick to stone building with great inertia.
Outdoor temperature averaging time -
24 hours.
10. Setting menu - System
Содержание ACD 03
Страница 1: ...Operation manual EN www atmos eu EN 1 ACD03 04 Operation manual ...
Страница 2: ...Operation manual EN www atmos eu ACD03 04 ...
Страница 8: ...Operation manual EN www atmos eu EN 8 ACD03 04 ...
Страница 265: ...Operation manual EN www atmos eu EN 265 ACD03 04 12 Overview of menus and their parameters ...