Operation manual - EN
www.atmos.eu
EN - 123
ACD03/04
10. Setting menu - Hydraulics
/F
unction configuration/Heating circuit 3 function
Example of activation (assignment) of ARU5 room unit (sensors) - RSc (a, b, d)
Example of assignment of sensors for temperature measurement for ARU10 and
ARU30 room units for heating circuit 3
INFO - If more sensors (from more room units for one heating circuit) are selected, the
controller shall work with their average value (T
RSEa
+ T
RSEb
/ 2).
ATTENTION -
The default setting when using
ARU10 and ARU30
room units for
circuit 3
is the
ARUc unit
and
RSEc sensor
.