• P05
System
parameter- Antifreeze protection temperature
If the average outdoor temperature falls below the set value, the anti-freeze protection is activated.
The pumps of the defined heating circuits (excluding DHW) do not switch off even when swit-
ching to setback mode or when the required room temperature is exceeded (
→
P09
Heating circuit
parameter). Heating circuits create demand for an energy source.
Use antifreeze protection for heating systems where pipes may freeze (for example, recreational
facilities, heating ducts, etc.). If there is no risk of the pipes freezing, the frost protection can be
switched off, but it is not recommended.
Antifreeze protection can be carried out by continuous or cyclic operation of heating circuits
(pumps) see menu System
→
- P25
System
and P26
System
parameter.
Factory default setting:
-5 °C
• P07
System
parameter - Enabling the temperature of comfort block of time program
In case of setting the
→
P07
System
parameter to
On
(factory default setting), up to 5 comfort
blocks (
Comfort
with own required room temperature) can be set up within one day time
program (24 hours).
INFO
- If a different temperature is set in
Comfort
mode, the relevant temperature setting
applies only
in the relevant block of time program
. The temperatures of individual blocks
are set in
→
0
24
Time Programs menu.
10. Setting menu - System