• P20
Heating circuit
parameter - I-range
The parameter is intended to set the integration component of the controller of mixed circuits:
MK, KR, FR and RLA type.
Factory default setting:
MK, FR, KR circuit type – 160 s
RLA circuit type – 240 s
INFO -
I-range = integration time to achieve the required value
(very short time = controller oscillation / very long time = long time to reach the requirement)
• P21
Heating circuit
parameter - Actuator speed
The parameter characterizes the speed of the actuator (rotation time from one extreme position to
another by an angle of 90°).
The parameter is displayed only for mixed circuits of MK, KR, FR and RLA type.
Factory default setting:
120 sek
CAUTION -
Always enter the actual speed of the actuator according to its data plate.
• P24
Heating circuit
parameter - D-range
The parameter is intended to set the derivative component of the controller of mixed circuits of
MK, KR, FR and RLA type.
Here, the smaller the value, the less it will affect the quality of the controller, too high value can
cause vibrations of the controller.
Factory default setting:
MK, FR, KR circuit type – 4,0 s
RLA – 15,0 circuit type s
INFO -
D-range = brake of reaction to change
(time too short = slow reaction to change / time too long = sharp reaction to change)
10. Setting menu - Heating circuit 1 / 2 / 3 / (4)
Содержание ACD 03
Страница 1: ...Operation manual EN www atmos eu EN 1 ACD03 04 Operation manual ...
Страница 2: ...Operation manual EN www atmos eu ACD03 04 ...
Страница 8: ...Operation manual EN www atmos eu EN 8 ACD03 04 ...
Страница 265: ...Operation manual EN www atmos eu EN 265 ACD03 04 12 Overview of menus and their parameters ...