Operation manual - EN
www.atmos.eu
EN - 261
ACD03/04
ACCUMULATION TANK menu
Parameter Description
Setting range / Setting value
Factory default setting
Setting
P01
PFmin minimum temperature
5 ‒ (P02 - 1 K)
40 °C
P02
PFmax maximum temperature
(P01 + 1 K) ‒ 110
110 °C
P03
Increasing filling requirement
0 ‒ 20 K
5 K
P04
PFmin switching difference
0 ‒ 50 K
2 K
P05
Enforced losses
Off / On
On
P08
Tank protection during discharge
Off / On
On
P09
Tank protection during charging
Off / On
On
P10
Tank operating mode
1 - accumulation
2 - buffer
according to selected hydraulic
diagram
P14
Minimal tank requirement value
5 ‒ 110 °C
70 °C
P15
Shutdown difference of the DKP protection
during charging
-10 ‒ 10 K
-3 K
P16
Switching difference of the DKP protection
during charging
-2 ‒ 10 K
0 K
SOURCES menu
Parameter Desription
Setting range / Setting value
Factory default setting
Setting
P04
EKstart default temperature
10 ‒ (P05 - 1 K)
40 °C
P05
EKmin minimum temperature
(P04 + 1 K) ‒ (P05 + 4 K)
80 °C
P06
EKdif shutdown difference
1 ‒ 7 K
3 K
P07
EKmax maximum temperature
(P05 + 4 K) ‒ 95 °C
95 °C
P08
DHW summer heating using EK
Off / On
Off
P09
EHP comfort operation
Off / On
On
P10
DHW summer heating using EHP
Off / On
Off
P11
EHP delayed start
0 ‒ 480 min
60 min
P16
Enforced losses EK
Off / On
On
P37
Source name
-
-
12. Overview of menus and their parameters
Содержание ACD 03
Страница 1: ...Operation manual EN www atmos eu EN 1 ACD03 04 Operation manual ...
Страница 2: ...Operation manual EN www atmos eu ACD03 04 ...
Страница 8: ...Operation manual EN www atmos eu EN 8 ACD03 04 ...
Страница 265: ...Operation manual EN www atmos eu EN 265 ACD03 04 12 Overview of menus and their parameters ...