Operation manual - EN
www.atmos.eu
EN - 224
ACD03/04
• P11
Sources
parameter - EHP delayed start
The parameter is intended to postpone the switching on of the electric heating of the accumulati-
on tank for the defined time, if there is a requirement of the heating circuits or the DHW heating
circuit (for example, the required time for firing up the boiler).
Factory default setting: 60 min
INFO
- P09
Sources
, P10
Sources
and P11
Sources
parameters are visible only after activation of the
function of the electrical heating of the EHP accumulation tank (
→
Hydraulics/Func-
tion configuration/Accumulation tank).
• P16
Sources
parameter - Enforced losses EK
The parameter is intended to switch on the protection function of the EK external boiler against
high temperature, which could cause its damage. The EK limit temperature is defined by
→
P07
Sources
parameter. Excess energy is transferred to the heating circuits with respect to the maxi-
mum allowed temperatures defined by
→
Pl3
Heating circuit
parameter
Factory default setting: On
INFO
- The function makes no difference when the EK external boiler is connected to the
heating circuit.
• P37
Source
parameter - Source name
The parameter allows the EK external boiler (source) to be named.
10. Setting menu - Sources