Operation manual - EN
www.atmos.eu
EN - 197
ACD03/04
• P26
System
parameter - Antifreeze protection - pause
The parameter is used to set the pause time of the pumps (all defined heating circuits) in case of
switching on the antifreeze protection ( snowflake on the display) defined by
→
P05
System
parameter (e.g. at -5 °C).
This is a function associated with P25
System
parameter.
Factory default setting:
Off
Setting options:
Off - pumps of defined heating circuits are permanently switched on
(P25
System
parameter = On)
Zap - On - pumps of defined heating circuits are stopped for a set time
(recommended factory setting 60 minutes)
(P25
System
parameter = On)
INFO
- In case of parameter setting of P25
System
= On and P26
System
= On, the pumps of all
defined heating circuits run in cycles (run / pause).
After the set time has elapsed, each defined circuit is switched on for the run time defined
by
→
P25
System
parameter.
CAUTION
- The pause time of the heating circuits should not be too long so that water in
the pipe cannot freeze or too short so that the room temperature would be exceeded.
• P28
System
parameter- Default parameter values
After confirmation, the values of some parameters in the controller will be set to the factory (de-
fault) values.
Namely: time programs -
factory settings - Mon - Fri 05:00 - 09:00, 14:00 - 22:00
Sat - Sun 07:00 - 10:00, 15:00 - 22:00
required temperatures
- factory settings - (
Setback 19 °C /
Comfor 23 °C)
CAUTION
- By setting the default values (by confirming
Yes
) of the parameters with the
technician
access password entered, all alarms will be reset.
10. Setting menu - System
Содержание ACD 03
Страница 1: ...Operation manual EN www atmos eu EN 1 ACD03 04 Operation manual ...
Страница 2: ...Operation manual EN www atmos eu ACD03 04 ...
Страница 8: ...Operation manual EN www atmos eu EN 8 ACD03 04 ...
Страница 265: ...Operation manual EN www atmos eu EN 265 ACD03 04 12 Overview of menus and their parameters ...