Operation manual - EN
www.atmos.eu
EN - 227
ACD03/04
• P07
Heating circuit
parameter - Heating limit (summer shutdown)
The parameter enables automatic shutdown of the heating circuit if the required (calculated) water
temperature flowing into the heating circuit approaches the room temperature, as defined by this
parameter.
The function is used in applications without an outdoor sensor or as a protection against overheating
of objects at low heat losses.
Factory default setting:
Off
• P08
Heating circuit
parameter - Frost protection room temperature
The parameter is intended to set the required room temperature in the
Holiday
or
Standby
working mode with respect to flowers, furniture, house equipment, etc
Factory default setting:
8 °C
• P09
Heating circuit
parameter - Room thermostat function
The parameter is intended to switch off the heating circuit when the required room temperature is
exceeded by the value defined by this parameter.
Factory default setting:
Off
INFO -
In case of active antifreeze protection (higher priority), the heating circuit will
never be switched off.
• P11
Heating circuit
parameter - Constant flow temperature
The parameter allows you to set the constant water temperature of the mixed circuit for the RLA,
FR and KR circuit types.
Factory default setting:
78 °C
• P12
Heating circuit
parameter - Minimum flow temperature
The parameter allows you to set the minimum temperature of the water flowing into the heating
circuit using the equithermal curve control (MK type mixed circuit).
The function affects the possible overheating of rooms in Setback modes.
Factory default setting:
15 °C
10. Setting menu - Heating circuit 1 / 2 / 3 / (4)