Operation manual - EN
www.atmos.eu
EN - 188
ACD03/04
Controlled boiler connected with accumulation tank
and heat pump
Example 23
- Hydraulic diagram:
37003
3
xxxx (controlled boiler) + x
7
xxx (DKP+DHW+ACC) + xx
0
xx (-) + xxx
0
x (-) + xxxx
3
(MK1)
Boiler controlled by the controller based on the boiler temperature (WF sensor) and flue gas temperature
(AGF sensor).
The ACD 03/04 controller controls boiler operation (fan - FAN / PRESS), the boiler circuit pump
(DKP) (Laddomat/thermoregulation valve), one heating circuit (MK1), charging and discharge of
accumulation (buffer) tank and the tank (boiler) for DHW heating (SLP) and operation of the heat
pump connected as electric heating of the accumulation tank (EHP).
INFO
- Heat pump connected as (EHP). (electric heating of the accumulation tank).
INFO1 temperature serves as information about temperature of the out coming water from
heat pump. It has no effect on its operation.
2 - 6 bar
10 - 15 °C
Max 60 °C
TV 60 °C (65/70/72/77 °C)
Laddmat 22
MK1
VF1
WF
ATMOS
ACD
ARU30
22,5 °c
DKP
MKP1
INFO1
EHP
SF
PF
SLP
AGF
FAN L
PF2
PF3
AF
10. Setting menu - Hydraulics - Hydraulic diagram