Operation manual - EN
www.atmos.eu
EN - 241
ACD03/04
• P17
DHW
parameter - SLP switching difference
The parameter is intended to set the switching difference of the SLP filling pump, if the source
temperature (boiler, accumulation tank, EK) increases above the current temperature of the DHW
tank by the defined value.
Factory default setting: 5 K
INFO
- The parameter is accessible only if
→
P08
DHW
parameter =
On
.
• P18
DHW
parameter - ESLP mode
The parameter is intended to set the function of automatic switching of the electric heating coil in
the DHW tank (boiler), if the heat source (boiler, accumulation tank, EK) is not able to ensure the
heating of the water in the DHW tank to the required temperature (low PF, WF, EKF temperature).
Factory default setting: 1
-
year-round
Setting options:
1 - year-round
– electro heating is allowed continuously, regardless of the outdoor temperature
2 - in winter
– electric heating of the DHW tank (boiler) is allowed only if the average
outdoor temperature is lower than the temperature defined by
→
P04
System
parameter
(Temperature of transition to summer mode)
3 - in summer
– electric heating of the DHW tank (boiler) is allowed only if the average
outdoor temperature is higher than the temperature defined by
→
P04
System
parameter
(Temperature of transition to summer mode)
• P19
DHW
parameter- ESLP filling time prolongation
The parameter allows you to prolong the operation of the electric heating of the DHW tank by a
defined time. It is a rundown of the heating element.
Factory default setting: Off
INFO
- The function is designed for DHW tanks with a heating element at the bottom and
an SF sensor located at the top.
• P37
DHW
parameter - DHW circuit name
The parameter is intended to name the DHW circuit by its own name.
10. Setting menu - DHW