Operation manual - EN
www.atmos.eu
EN - 99
ACD03/04
→
Hydraulics/Function configuration
Domestic water DHW (2)
submenu - overview of defined elements:
The controller allows the control of two tanks for DHW heating (DHW and DHW2).
All functions and control methods are the same for both DHW tanks.
Activation or deactivation of the domestic hot water (DHW) control is set in the submenu
DHW domestic water / DHW - tank = Yes / No
DHW2 domestic water / DHW2 - tank = Yes / No
Circuit connection type
- allows setting the type of DHW circuit connection to one heating
circuit.
The function can be set (visible) only after its activation in the submenu -
Domestic water
DHW (2)/Control circuit connection = Yes
WARNING - The DHW circuit can never be the control circuit for the MK and DK
heating circuits. Requirement for DHW domestic hot water heating is in practice
completely different from the requirements for heating circuits.
SF
sensor
- DHW tank sensor (NTC sensor 20 kΩ)
- temperature required to control the
heating of the domestic hot water tank (DHW). Installation of the sensor in the middle or in
the upper half of the domestic hot water tank (DHW boiler).
SF2
sensor -
DHW 2nd tank sensor (NTC sensor 20 kΩ)
- temperature required to control the
heating of the domestic hot water tank (DHW). Installation of the sensor in the middle or in
the upper half of the domestic hot water tank (DHW boiler).
10. Setting menu - Hydraulics
/F
unction configuration/Domestic water DHW