Operation manual - EN
www.atmos.eu
EN - 205
ACD03/04
• P16
Boiler
parameter - Enforced boiler losses
The parameter is used to enable the
boiler protection function against overheating
when
exceeding the KTmax maximum (critical) boiler temperature defined by
→
P03
Boiler
parameter.
Factory default setting: On
INFO
- If the boiler temperature KTmax is exceeded, excess energy is conducted into the
heating circuits, the accumulation tank and the DHW tank (limits: heating circuit
→
P13
Heating circuit
parameter,
→
P02
Accumulation tank
parameter, DHW
→
P06
DHW
parameter).
• P17
Boiler
parameter - DKP control
The parameter is intended to set the method of control of the DKP pump in the boiler circuit.
Switching the DKP pump on and off according to selected sensors (WF / AGF temperatures) and
functions (BRE).
Factory default setting:
- for boiler with manual stoking and combined boilers (DCxxSP, DCxxGSP): 2 - according to WF and AGF
- for automatic pellet boiler: 1 - according to WF
- for not controlled boiler: 1 - according to WF
Setting options:
1 – according to WF
- control (switching) of the pump in the boiler circuit according to the
WF boiler temperature. Defined by
→
P04
Boiler
parameter.
2 – according to WF and AGF flue gas temperature
- control (switching) of the pump
in the boiler circuit according to the WF boiler temperature and AGF flue gas
temperature.
The pump in the boiler circuit is switched on when the boiler temperature is reached.
By
→
P04
Boiler
parameter and minimum flue gas temperature
→
P18
Boiler
parameter.
INFO -
Control according to WF and AGF is recommended for all boilers with manual
stoking and wood and pellets combined boilers (DCxxSP(X), DCxxGSP).
3 – according to WF and BRE
-
control (switching) of the pump in the boiler circuit according
to the WF boiler temperature and control "burner L2 phase" - BRE output.
The pump in the boiler circuit is switched on when the boiler temperature is
reached.
→
P04
Boiler
parameter and switched control "burner L2 phase" - BRE
output. After switching off the "burner L2 phase" - BRE output, the DKP pump is
switched off with a delay, e.g. 10 minutes (
→
P19
Boiler
parameter).
INFO -
Control according to WF and BRE is recommended for all pellet boilers.
10. Setting menu - Boiler