10. Setting menu - Hydraulics
/F
unction configuration/Boiler
AGF
–
activation of flue gas temperature measuring
(AGF / PT1000 sensor) - designed for
not controlled boilers (hydraulic diagram 1xxxx) and boilers with BRE burner (for pellets)
(hydraulic diagram 2xxxx), which do not require flue gas temperature measuring for their
function (AGF sensor is not automatically defined for these boilers).
INFO
- To measure high temperatures, it is necessary to use a suitable sensor with a sufficient
temperature range and install this sensor in a suitable place to prevent damage.
ATTENTION -
If the AGF
flue gas temperature sensor is not
connected for a boiler with
manual stoking, the controller is
not able
to control the fan operation (boiler function). The
boiler must be set up and connected as "Not controlled"
. Setting is performed only in
the
→
Hydraulics/Hydraulic diagram overview/Controlled boiler =
Yes / No
menu.
Depending on the location of the sensor, the reference (on the flue-gas duct) or real
(in the pocket of the flue-gas duct) flue gas temperature is displayed on the controller
display.
An undefined function (unassigned terminal) is displayed with a warning sign.
INFO -
In case of addition of a new function to the input or output, it is always necessary
to assign a specific terminal (define location) to the function.
AIW – automatic wood ignition –
function designed for 3 and 5 boiler types. When selecting
the type of
boiler with ignition
, the function is automatically activated. To set the type
of the boiler, go to the menu
→
Hydraulics/Hydraulic diagram overview/Boiler type
designation (e.g. DC25GD with ignition). The function can be additionally switched on in the
menu
→
Hydraulics/Function configuration/Boiler/AIW – Automatic wood ignition.
For boilers with AIW function, additional functions can be activated:
-
SAI – switching contact for AIW
(for terminals – VI1, VI2, VI3, VI4, VI5) –
allows remote control by any potential-free device (GSM, WiFi). In ON states – closed
terminals / in OFF states – open terminals.
-
SAIH – switching contact for AIW
(for terminals – DVI1, DVI2) – allows remote
control by any device (GSM, WiFi – voltage 230 V / 50 Hz). In ON / OFF mode.