ACD03/04
• P02
Heating circuit
parameter - Equithermal curve (Heating system temperature exponent)
The parameter allows the equithermal curve (temperature exponent) to be set according to the type
of heating system and the character of the building.
The exponent of the equithermal curve expresses the curve bending and is determined by the type
of heating system (underfloor heating, radiators, convectors).
Recommended setting:
1,0 … 1,3
-
underfloor heating -
heating system with low temperatures, with high inertia
and slow rise of room temperature
1,3 … 2,0
-
radiator heating -
heating system with medium temperatures and medium
inertia of the system
2,0 … 3,0
-
convector heating -
with forced airflow (fan-coil saharas) - heating system with
high temperatures and low inertia of the system
INFO -
Correct calculation of the flow temperature to the heating circuit affects the
dimensioning of the heating system and the thermal loss of the object
Outdoor temperature AF
average
(°C)
exponent 1, room temperature 20 °C
exponent 1.5, room temperature 20.5 °C
exponent 2.0, room temperature 21 °C
exponent 2.5, room temperature 21,5 °C
exponent 3.0, room temperature 22 °C
Room temperature
Relationship of the flow temperature of the circuit to the outdoor temperature according to the equithermal curve
and the room temperature requirement
20
15
15,0
20,0
25,0
30,0
35,0
40,0
45,0
50,0
55,0
60,0
65,0
70,0
75,0
80,0
85,0
90,0
10
5
0
-5
-10
-15
-20
Circuit flow temperature (setpoint VF) S
WF
(°C)
10 °C
30 °C
INFO -
The requirement for a higher room temperature moves the curve diagonally upwards.
10. Setting menu - Heating circuit 1 / 2 / 3 / (4)