Operation manual - EN
www.atmos.eu
EN - 202
ACD03/04
• P06
Boiler
parameter - FAN, PRESS, BRE switching difference
The parameter is used to set the switching difference of the exhaust (pressure) boiler fan and pellet
burner.
Factory default setting: 3 K
INFO
- Boiler (fan / burner) operation therefore takes place in the temperature range -
calculated required temperature minus switching difference
→
P06
Boiler
(on) parameter
to calculated required boiler temperature
→
P02
Boiler
(off) parameter.
• P07
Boiler
parameter - Max. flue gas temperature FAN, PRESS
The parameter allows you to set the maximum recommended flue gas temperature with respect
to the guaranteed boiler efficiency. If the actual flue gas temperature is higher than the set value
for more than 60 minutes, a logical Alarm is started to alert the user to the need to clean the boiler
exchanger.
Factory default setting: Off
INFO
- Logical Alarm (message) does not affect any function of the ACD03/04 controller,
it only serves for information purposes. The alarm automatically stops when the flue gas
temperature decreases.
• P08
Boiler
parameter- FAN fire up time
The parameter is used for boilers with manual stoking (with fan) to set the maximum time required
for firing up after starting the boiler, which is started by clicking on the
button (hand).
If the AGFmin minimum flue gas temperature defined by
→
P18
Boiler
parameter is not reached
after the fire up time defined by
→
P08
Boiler
parameter has elapsed, the boiler (fan) is switched
off.
If the AGFmin minimum working temperature of the flue gas defined by
→
P18
Boiler
parameter
is reached, the controller is switched to normal operation.
Factory default setting: 60 min
INFO
- If removing ash or cleaning the boiler in a cold state, the fan will be switched
off after the set time. If the fan is required to be switched off earlier, click again on the
button (hand).
10. Setting menu - Boiler
Содержание ACD 03
Страница 1: ...Operation manual EN www atmos eu EN 1 ACD03 04 Operation manual ...
Страница 2: ...Operation manual EN www atmos eu ACD03 04 ...
Страница 8: ...Operation manual EN www atmos eu EN 8 ACD03 04 ...
Страница 265: ...Operation manual EN www atmos eu EN 265 ACD03 04 12 Overview of menus and their parameters ...