EN - 206
ACD03/04
• P18
Boiler
parameter - AGFmin minimal flue gas temperature
The parameter is used to set the minimum flue gas temperature AGFmin, which value defines the
transition
from firing up to normal operation and from operation to burnout
for boilers with
manual stoking and combined wood and pellet boilers (DCxxSP(X), DCxxGSP).
If the required minimum flue gas temperature is not reached during the firing up as defined
by
→
P08
Boiler
parameter, the boiler is switched off (decommissioned). If the flue gas
temperature drops below the set value (fuel burnout) during operation, the boiler is switched off
(decommissioned).
Factory default setting: 80 °C
INFO -
Based on this parameter (meeting the condition), the operation of the boiler fan
(FAN, PRESS) and the DKP boiler circuit pump (
→
P17
Boiler
parameter = 2) is controlled.
• P19
Boiler
parameter - DKP rundown after BRE burnout
The parameter is intended to set the pump rundown time in the DKP boiler circuit for automatic
boilers with BRE burner when set by
→
P17
Boiler
parameter =
3 - according to WF and
BRE
. This is a variant of the pump control in the DKP boiler circuit depending on the WF water
temperature and the logic of the burner.
Factory default setting: 10 min
INFO -
The setting is mainly used for devices (boilers) that have a large inertia to prevent
them from overheating (opening the safety thermostat).
• P20
Boiler
parameter - Boiler protection according to DKP
The parameter serves as a safety device against unintentional operation of the heating circuits and
the DHW heating circuit when connected
without the accumulation tank
.
Setting options:
On
– all heated circuits (pumps) are not in operation, if the DKP pump in the boiler circuit is
not in operation.
Connection without the accumulation tank or with the buffer (small) tank.
Off
– all heated circuits (pumps) are operated regardless of the pump operation in the DKP
boiler circuit.
Connection with accumulation tank.
Factory default setting: according to hydraulic diagram
INFO -
Functions (logics) associated with
→
P20
Boiler
parameter work the same even if
the DKP pump in the boiler circuit is not defined.
10. Setting menu - Boiler